Functions > Protection > 59N > Gn 59NIT-n
Parameter Range Settings
Default Gn1 Gn2 Gn3 Gn4
Delay 0 to 20 s Δ 0.01 s 5 s
Reset IEC/ANSI Decaying
0 to 60 s Δ 1 s
IEC 61850 Functional Information Mapping
A59NITPTOV*.Mod
Information
59N Overvoltage Enabled (Function Config) x 0 1 1
Element Disabled 1 x 0 0
Element Inhibited x x 1 0
A59NITPTOV*.Mod.stVal 5 5 2 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
Irrelevant: x
IEC 61850 Value ON: 1
BLOCKED: 2
TEST: 3
TEST/BLOCKED: 4
OFF: 5
A59NITPTOV*.Health
Information
Device Healthy 0 1
A59NITPTOV*.Health.stVal 3 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value OK: 1
WARNING: 2
ALARM: 3
A59NITPTOV*.Op
Information
Element Operated 0 1
A59NITPTOV*.Op.general 0 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value TRUE: 1
FALSE: 0
5.23.6
Protection and Automation Functions
5.23 59N Neutral Voltage Displacement
Reyrolle 7SR5, Overcurrent Protection Device, Device Manual 317
C53000-G7040-C014-1, Edition 11.2019