EasyManua.ls Logo

Siemens 7SR51 - Page 327

Siemens 7SR51
556 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
[dw_7SR5_function67ApplicationAndSettingNotes1, 1, en_US]
Figure 5-38
Phase Fault Directional Characteristic
Parameter: 67 > Minimum Voltage
Default setting: 1 V
Where the measured polarizing voltage is below this setting no directional control signal is given and
operation of protection elements set as directional will be inhibited. This prevents mal-operation under
fuse failure/MCB tripped conditions where noise voltages can be present.
Parameter: 67 > 2-out-of-3 Logic
Default setting: Disabled
When set to Enabled, the directional elements will only operate for the majority direction, e.g. if I
a
and I
c
are detected as forward flowing currents and I
b
is detected as reverse current flow, then directional
enable signals 67 FWD PhA and 67 FWD PhC will operate while phase the phase B directional enable
signal will be inhibited.
Parameter: 67G > Char Angle
Default setting: -15°
The 67G directional element provides forward and reverse outputs that can be used to control each
measured earth fault element.
The measured directional earth fault elements use the zero phase sequence (V
0
) voltage as the reference
quantity and the zero phase sequence current (I
0
) phasor is the operate quantity.
I (Operate)
V (Reference)
I
0
V
0
Protection and Automation Functions
5.25 67 Directional Overcurrent/Earth Fault
Reyrolle 7SR5, Overcurrent Protection Device, Device Manual 327
C53000-G7040-C014-1, Edition 11.2019

Table of Contents

Related product manuals