Functions > Protection > 67 > Gn 67G
Parameter Range Settings
Default Gn1 Gn2 Gn3 Gn4
Char Angle -95° to +95°, Δ 1° -15°
Minimum Voltage 0.33 V to 67 V, Δ 0.5 V 0.33 V
Functions > Protection > 67 > Gn 67GS
Parameter Range Settings
Default Gn1 Gn2 Gn3 Gn4
Char Angle -95° to +95°, Δ 1° -15°
Minimum Voltage 0.33 V to 67 V, Δ 0.5 V 0.33 V
Compensated Network Enabled
Disabled
Disabled
Wattmetric Enabled
Disabled
Disabled
Wattmetric Power 0.05 to 20 ⋅ I
rated
⋅ W, Δ 0.05
⋅ I
rated
⋅ W
0.1 ⋅
I
rated
⋅ W
Ires Select Ires
Ires Real
Ires
Functions > Protection > 67 > Gn 67N
Parameter Range Settings
Default Gn1 Gn2 Gn3 Gn4
Polarizing Quantity NPS
ZPS
ZPS
Char Angle -95° to +95°, Δ 1° -15°
Minimum Voltage 0.33 V to 3 V, Δ 0.5 V 0.33 V
Information List
Input/Output Matrix
General Pickup User Logic Type
67 FWD PhA Output
67 REV PhA Output
67 FWD PhB Output
67 REV PhB Output
67 FWD PhC Output
67 REV PhC Output
67G FWD Output
67G REV Output
Inhibit Wattmetric Input
67GS FWD Output
67GS REV Output
Wattmetric Po> Operated Output
67N FWD Output
67N REV Output
The complete serial protocol information list containing the DNP3, IEC 60870-5-103, and Modbus RTU data
information for the configured device can be generated using the Export Report feature in the Reydisp
Manager 2 tool, Serial Comms & Events.
5.25.6
Protection and Automation Functions
5.25 67 Directional Overcurrent/Earth Fault
336 Reyrolle 7SR5, Overcurrent Protection Device, Device Manual
C53000-G7040-C014-1, Edition 11.2019