Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
Irrelevant: x
IEC 61850 Value ON: 1
BLOCKED: 2
TEST: 3
TEST/BLOCKED: 4
OFF: 5
A81PTUF*.Health
Information
Device Healthy 0 1
A81PTUF*.Health.stVal 3 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value OK: 1
WARNING: 2
ALARM: 3
A81PTUF*.Op
Information
Element Operated 0 1
A81PTUF*.Op.general 0 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value TRUE: 1
FALSE: 0
A81PTUF*.Str
Information
Element picked up 0 1
A81PTUF*.Str.general 0 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value TRUE: 1
FALSE: 0
A81PTOF*.Mod
Information
81 Frequency Enabled (Function Config) x 0 1 1
Element Disabled 1 x 0 0
Element Inhibited x x 1 0
A81PTOF*.Mod.stVal 5 5 2 1
Protection and Automation Functions
5.27 81 Frequency Protection – "f>" or "f<"
Reyrolle 7SR5, Overcurrent Protection Device, Device Manual 347
C53000-G7040-C014-1, Edition 11.2019