60VTS VT Supervision
Overview of Functions
The 60VTS Voltage Transformer Supervision function is used to:
Detect the loss of voltage supply due to VT fuse operation on 1, 2 or 3 phases
Provide a delayed alarm for indication purposes
Can be used to automatically inhibit protection elements that could be adversely affected by the resulting
erroneous voltage
Can be used to automatically switch directional protection elements to be non-directional during failed
fuse conditions
Structure of the Function
The VT supervision function has group dependent settings. These settings can be different in each settings
group – group numbers (Gn) 1 to 4.
The function monitors the VT using the 3 phase VT inputs e.g. VT1/2/3 and 3 phase CT inputs e.g. CT1/2/3. The
fundamental frequency component are measured from processing of the measured samples.
The pickup output from the 60VTS function element is used internally to block selected protection elements.
1 or 2 Phase Failure Detection
The presence of negative phase sequence (NPS) or zero phase sequence (ZPS) voltage in a power system is
normally accompanied by NPS or ZPS current. The presence NPS or ZPS voltages without the corresponding
level of NPS or ZPS current can indicate a failure of 1 or 2 VT phases.
3 Phase Failure Detection
During normal load conditions PPS voltage and PPS load currents are measured within operating limits. Meas-
urement of PPS load without corresponding PPS voltage can indicate 3 phase VT failure. To ensure these
conditions are not caused by a 3 phase fault the PPS current must also be below the fault level.
The VT is considered to have failed where positive sequence voltage is below 60VTS V
1
while positive
sequence current is above I
1
load and below I
1
fault level.
External MCB
A binary input can be set as Ext Trig 60VTS to allow the 60VTS Delay element to be started from an
external MCB operating.
Once a VT failure condition has occurred the output is latched on and is reset by any of the following:
Voltage is restored to a healthy state i.e. above V
1
setting while NPS or ZPS voltage is below V setting
Ext Reset 60VTS – A binary or virtual input, or function key and a VT failure condition no longer exists
Inhibit 60VTS – A binary or virtual input
6.3
6.3.1
6.3.2
Supervision Functions
6.3 60VTS VT Supervision
Reyrolle 7SR5, Overcurrent Protection Device, Device Manual 379
C53000-G7040-C014-1, Edition 11.2019