EasyManua.ls Logo

Siemens 7SR51 - Page 417

Siemens 7SR51
556 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Q0XCBR*.BlkOpn
Information
CB Control Open Block 0 1
Q0XCBR*.BlkOpn.stVal 0 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value TRUE: 1
FALSE: 0
Q0XCBR*.BlkOpCnt
Information Measurand Value
CB Operations Counter Q0XCBR*.OpCnt.stVal 0 to 10000
Q0XCBR*.Pos
Information
CB Status Open 0 1 0 1
CB Status Closed 0 0 1 1
Q0XCBR*.Pos.stVal 00 01 10 11
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value INTERMEDIATE STATE: 00
OFF: 01
ON: 10
INVALID STATE: 11
Q0XCBR*.SumSwARs1
Information
Measurand Value
CB Wear PhA Q0XCBR*. SumSwARs1.stVal 0 to 10000
Q0XCBR*.SumSwARs2
Information
Measurand Value
CB Wear PhB Q0XCBR*. SumSwARs2.stVal 0 to 10000
Q0XCBR*.SumSwARs3
Information
Measurand Value
CB Wear PhC Q0XCBR*. SumSwARs3.stVal 0 to 10000
Q0CSWI1.Mod
Information
Reset Device x
Q0CSWI1.Mod.stVal 1
Control Functions
7.2 52 Circuit-Breaker Control
Reyrolle 7SR5, Overcurrent Protection Device, Device Manual 417
C53000-G7040-C014-1, Edition 11.2019

Table of Contents

Related product manuals