Functions > Control > 79 > 79PF
Parameter Range Settings
Default Gn1 Gn2 Gn3 Gn4
PF Protection Trip 2 Inst
Delayed
Inst
PF Protection Trip 3 Inst
Delayed
Delayed
PF Protection Trip 4 Inst
Delayed
Delayed
PF Protection Trip 5 Inst
Delayed
Delayed
PF HS Trips <none>
50-n
51-n
<none>
PF Delayed Trips <none>
50-n
51-n
<none>
PF HS Trips to LO Target 1 to 5 5
PF Delayed Trips to LO
Target
1 to 5 5
Functions > Control > 79 > 79EF
Parameter Range Settings
Default Gn1 Gn2 Gn3 Gn4
EF Triggers 50-n
51-n
<all>
EF Trips to LO Target 1 to 5 5
EF Deadtime 1 0 to 20 s Δ 0.01 s
20 to 100 s Δ 0.1 s
100 to 1000 s Δ 1 s
1000 to 10000 s Δ 10 s
10000 to 14400 s Δ 100 s
5 s
EF Deadtime 2 0 to 20 s Δ 0.01 s
20 to 100 s Δ 0.1 s
100 to 1000 s Δ 1 s
1000 to 10000 s Δ 10 s
10000 to 14400 s Δ 100 s
5 s
EF Deadtime 3 0 to 20 s Δ 0.01 s
20 to 100 s Δ 0.1 s
100 to 1000 s Δ 1 s
1000 to 10000 s Δ 10 s
10000 to 14400 s Δ 100 s
Delayed
5 s
EF Deadtime 4 0 to 20 s Δ 0.01 s
20 to 100 s Δ 0.1 s
100 to 1000 s Δ 1 s
1000 to 10000 s Δ 10 s
10000 to 14400 s Δ 100 s
5 s
Control Functions
7.3 79 Automatic Reclosing
434 Reyrolle 7SR5, Overcurrent Protection Device, Device Manual
C53000-G7040-C014-1, Edition 11.2019