Functions > Control > 79 > 79Extern
Parameter Range Settings
Default Gn1 Gn2 Gn3 Gn4
PF Protection Trip 1 Inst
Delayed
Inst
PF Protection Trip 2 Inst
Delayed
Inst
PF Protection Trip 3 Inst
Delayed
Delayed
PF Protection Trip 4 Inst
Delayed
Delayed
PF Protection Trip 5 Inst
Delayed
Delayed
Extern Trips to LO Target 1 to 5 5
Functions > Control > 79 > 79 SOTF
Parameter Range Settings
Default Gn1 Gn2 Gn3 Gn4
PF SOTF Trip Inst
Delayed
Inst
EF SOTF Trip Inst
Delayed
Inst
GS SOTF Trip Inst
Delayed
Inst
Extern SOTF Trip Not Blocked
Blocked
Not
Blocked
IEC 61850 Functional Information Mapping
A79RREC*.Mod
Information
Reset Device x x x x x
Autoreclose In 1 0 x 1 0
Autoreclose Out 0 1 x 1 0
Autoreclose Blocked 0 0 1 0 0
A79RREC*.Mod.stVal 1 1 2 1 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
Irrelevant: x
IEC 61850 Value ON: 1
BLOCKED: 2
TEST: 3
TEST/BLOCKED: 4
OFF: 5