A79RREC*.Health
Information
Device Healthy 0 1
A79RREC*.Health.stVal 3 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value OK: 1
WARNING: 2
ALARM: 3
A79RREC*.Op
Information
Autoreclose Operated 0 1
A79RREC*.Op.general 0 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value TRUE: 1
FALSE: 0
A79RREC*.AutoRecSt
Information
79 In Progress 0 1 0
79 Successful AR 0 0 1
A79RREC*.AutoRecSt.stVal 1 2 3
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value READY: 1
IN PROGRESS: 2
SUCCESSFUL: 3
CNTLOGGIO1.Mod
Information
Reset Device x
CNTLOGGIO1.Mod.stVal 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
Irrelevant: x
IEC 61850 Value ON: 1
BLOCKED: 2
TEST: 3
TEST/BLOCKED: 4
OFF: 5
Control Functions
7.3 79 Automatic Reclosing
438 Reyrolle 7SR5, Overcurrent Protection Device, Device Manual
C53000-G7040-C014-1, Edition 11.2019