Device Configuration
Overview of Functions
The device configuration parameters are used to parameterize selected basic operating functionality of the
device.
The Reydisp Manager PC tool is used to configure the device.
Structure of the Function
The settings applied here are common to all function element settings groups i.e. settings group 1 (Gn1) to
settings group 4 (Gn4).
The device configuration covers a number of operating modes including:
Power system rated frequency
Display operating modes including settings, meters, fault and alarm alerts
Time setting and methods of time synchronizing
Local, remote and in-service operating modes
User identification
Logic of the Function
[lo_7SR5_DeviceConfiguration_OperatingMode, 1, en_US]
Figure 3-3 Device Configuration > Operating Mode
Application and Setting Notes
Parameter: System Frequency
Default Setting: 50 Hz
This setting is selected to be equal to the power system rated frequency.
i
i
NOTE
Changing the parameter will cause the device to restart.
3.2
3.2.1
3.2.2
3.2.3
3.2.4
Device Functionality
3.2 Device Configuration
Reyrolle 7SR5, Overcurrent Protection Device, Device Manual 49
C53000-G7040-C014-1, Edition 11.2019