Parameter: Select Grp Mode
Default Setting: Edge Triggered
This setting is applicable when an assigned binary input is used to select a settings group. See Input
Config > Input Matrix > Select Group n.
When operated the active settings group can be set to 1 (Gn1), 2 (Gn2), 3 (Gn3) or 4 (Gn4). The select
group mode is defined as follows:
Level triggered: the selected settings group is operational only whilst the input is energized.
Edge triggered: the selected settings group is enabled by the leading edge of the binary input operating
pulse and remains latched in regardless of the status of the binary input.
i
i
NOTE
Only 1 group should be energized at any time. If a second group is selected simultaneously the second
selection is ignored, even if the first subsequently resets. When a level triggered selection is reset, the relay
will return to the previously active group.
Parameter: Operating Mode
Default Setting: Local or Remote
Table 3-2 Operation Mode
Operation Remote Local Out of Service
Control
Rear RS485 port (set as Remote) Enabled Disabled Disabled
Rear RS485 port (set as Local) Disabled Enabled Disabled
Rear ethernet ports (set as Remote) Enabled Disabled Disabled
Rear ethernet ports (set as Local) Disabled Enabled Disabled
Fascia (Control mode) Disabled Enabled Disabled
Front USB port (set as Remote) Enabled Disabled Disabled
Front USB port (set as Local) Disabled Enabled Disabled
Control and test reset– Fascia Enabled Disabled Disabled
Binary inputs (set as Enabled in Remote) Enabled Disabled Disabled
Binary inputs (set as Enabled in Local) Disabled Enabled Disabled
Binary inputs (set as Out of Service) Disabled Disabled Enabled
Binary outputs Enabled Enabled Disabled
Mimic Screen Controls
Reporting
Spontaneous
IEC 60870-5-103 Enabled Enabled Disabled
DNP3 Enabled Enabled Disabled
General Interrogation
IEC 60870-5-103 Enabled Enabled Disabled
DNP3 Enabled Enabled Enabled
MODBUS Enabled Enabled Enabled
Changing of settings
Rear RS485 port (set as Remote) Enabled Disabled Enabled
Rear RS485 port (set as Local) Disabled Enabled Enabled
Device Functionality
3.2 Device Configuration
Reyrolle 7SR5, Overcurrent Protection Device, Device Manual 53
C53000-G7040-C014-1, Edition 11.2019