Configuration > Device Config
Parameter Range Default Setting
View/edit group 1, 2, 3, 4 1
Setting dependencies Enabled
Disabled
Disabled
Favorite meters timer Off, 1, 2, 5, 10, 15, 30, 60 min 60 min
Backlight timer Off, 1, 2, 5, 10, 15, 30, 60 min 5 min
Date DD/MM/YYYY
Time HH:MM:SS
Master time source None, ethernet, binary input, serial
(COM1)
Master time sync lost delay 1 to 90 min, Δ 1 min 60 min
Backup time source None, ethernet, binary input, serial
(COM1)
None
Backup time sync lost delay 1 to 90 min, Δ 1 min 60 min
CT1/2/3 settings display ⋅ I
rated
, primary, secondary ⋅ I
rated
CT4 settings display ⋅ I
rated
, primary, secondary ⋅ I
rated
Export power/Lag VAr +ve/+ve, +ve/-ve, -ve/+ve, -ve/-ve +ve/+ve
Select group mode Edge triggered, level triggered Edge triggered
Clock sync from BI None, seconds, minutes None
Operating mode Out of service, local, remote, local
or remote
Local or remote
Disk activity symbol Enabled
Disabled
Disabled
Unexpected Restart blocking Enabled
Disabled
Disabled
Unexpected restart count 1 to 20 3
Unexpected restart period 1 hr to 100 hr 1 hr
Device restart count type (111) Power on, expected, unex-
pected
111
Device restart count target 0 to 100000 100
Trip alert Enabled
Disabled
Enabled
General alarm alert Enabled
Disabled
Enabled
Relay identifier <16 characters maximum> 7SR5
Circuit identifier <16 characters maximum> <None>
Setting ID Not active
Control ID Not active
Reset passwords No
Device Functionality
3.2 Device Configuration
Reyrolle 7SR5, Overcurrent Protection Device, Device Manual 57
C53000-G7040-C014-1, Edition 11.2019