Parameter: VT1/2/3 Ratio Prim
•
Default setting: 132000 V
The setting value is used (in conjunction with VT1/2/3 Ratio Sec setting) by the device instrumenta-
tion e.g. to display primary voltage values.
Parameter: VT1/2/3 Ratio Sec
•
Default setting: 110 V
The setting value is used (in conjunction with VT1/2/3 Ratio Prim setting) by the device instrumen-
tation e.g. to display primary voltage values.
Parameter: VT1/2/3 Nominal
•
Default setting: 63.5 V
This is set to the rated voltage applied to the VT input. The setting will be dependent on the VT Config
setting e.g. phase-phase or phase-neutral Volts may be connected to the VT inputs.
Device Functionality
3.3 CT and VT Inputs