Loading...
Parameter: VT1/2/3 Config
Default setting: Van, Vbn, Vcn
This setting provides the device with the correct voltage inputs i.e. provides inputs configuration appro-
priate to the switchgear VT connections. The VT connections and required settings are illustrated in
Figure 3-7.
Note that the switchgear VT connection may affect the functionality that can be used in the device on the
system e.g. The VT1/2/3 configuration Va, Vb, Vc in Figure 3-7 does not allow zero sequence voltage V
0
to
be measured and so functions requiring this quantity cannot be used when this VT configuration is
selected.
[lo_7SR5_VTConnections, 1, en_US]
Figure 3-7
Illustration of VT Configuration Settings and VT Connections (Typical)
Device Functionality
3.3 CT and VT Inputs
Reyrolle 7SR5, Overcurrent Protection Device, Device Manual 63