Parameter: Phase Rotation
Default setting: ABC
This setting can be used when the device is used with primary systems having reverse phase rotation.
This allows the device functionality to operate correctly on these systems.
Settings Menu
Configuration > System Config
Parameter Range Default Setting
CT1/2/3 Nominal 1 A/5 A 1 A
CT1/2/3 Ratio Prim 000000 to 999999 2000 A
CT1/2/3 Ratio Sec 0.2 to 7 1
CT4 Nominal 1 A/5 A 1 A
CT4 Ratio Prim 000000 to 999999 2000 A
CT4 Ratio Sec 0.2 to 7 1
VT1/2/3 Config Va, Vb, Vc/Van, Vbn, Vcn/Vab, Vbc,
3V0
Van, Vbn, Vcn
VT1/2/3 Nominal 40 V to 160 V 63.5 V
VT1/2/3 Ratio Prim 000000 to 999999 132000 V
VT1/2/3 Ratio Sec 40 V to 160 V 110 V
VT1/2/3 Trim Magnitude 0 V to 20 V 0 V
VT1/2/3 Trim Angle -45° to +45°
VT4 Nominal 40 V to 160 V 63.5 V
VT4 Ratio Prim 000000 to 999999 132000 V
VT4 Ratio Sec 40 V to 160 V 110 V
VT4 Trim Magnitude 0 V to 20 V 0 V
VT4 Trim Angle -45° to +45°
Phase Rotation ABC, ACB ABC
3.3.4
Device Functionality
3.3 CT and VT Inputs
64 Reyrolle 7SR5, Overcurrent Protection Device, Device Manual
C53000-G7040-C014-1, Edition 11.2019