EasyManua.ls Logo

Siemens 7SR51 - Page 70

Siemens 7SR51
556 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter: 50BF-n Ext Trip
Default Setting: <None>
Used to trigger the circuit‑breaker fail function. The measured current must be above the 50BF setting for
the function to operate, (see 6 Supervision Functions , section 50BF Circuit-Breaker Failure Protection – 3
Pole).
Parameter: CB-n Open
Default Setting: <None>
This input is used to monitor the CB status. It is operated when the associated CB is open e.g. it is
connected to a CB auxiliary switch that is closed when the CB is open, (see 7 Control Functions, section
52 Circuit-Breaker Control).
Parameter: CB-n Closed
Default Setting: <None>
This input is used to monitor the CB status. It is operated when the associated CB is closed e.g. it is
connected to a CB auxiliary switch that is closed when the CB is closed, (see 7 Control Functions, section
52 Circuit-Breaker Control).
Parameter: Open CB-n
Default Setting: <None>
Operation of the binary input is used to initiate a CB open command, (see 7 Control Functions, section 52
Circuit-Breaker Control).
Parameter: Close CB
Default Setting:
Operation of the binary input is used to initiate a CB close command, (see 7 Control Functions, section 52
Circuit-Breaker Control).
Parameter: Inhibit CB-n Open
Default Setting: <None>
This setting is used to block the opening of a CB e.g. due to low stored energy, (see 7 Control Functions,
section 52 Circuit-Breaker Control).
Parameter: 74TCS-n
Default Setting: <None>
This setting is used when the binary input is connected in the CB trip circuit monitoring scheme wiring,
(see 6 Supervision Functions , section 74TC Trip-Circuit Supervision).
Parameter: 79 Trip & Reclose
Default Setting: <None>
See 7 Control Functions, section 79 Automatic Reclosing.
Parameter: 79 Trip & Lockout
Default Setting: <None>
See 7 Control Functions, section 79 Automatic Reclosing.
Device Functionality
3.4 Binary Inputs
70 Reyrolle 7SR5, Overcurrent Protection Device, Device Manual
C53000-G7040-C014-1, Edition 11.2019

Table of Contents

Related product manuals