PTRC1.Tr
Information
Trip operated (as configured to trip contact) 0 1
PTRC1.Tr.general 0 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value FALSE: 0
TRUE: 1
PTRC1.OpCntRs
Information
Resettable operations counter Measured Value
PTRC1.OpCntRs.stVal Value
Virtual Inputs/Outputs
VGGIO1.Mod
Information
Reset Device x
VGGIO1.Mod.stVal 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
Irrelevant: x
IEC 61850 Value ON: 1
BLOCKED: 2
TEST: 3
TEST/BLOCKED: 4
OFF: 5
VGGIO1.Health
Information
Device Healthy 0 1
VGGIO1.Health.stVal 3 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value OK: 1
WARNING: 2
ALARM: 3
Device Functionality
3.5 Binary Outputs
Reyrolle 7SR5, Overcurrent Protection Device, Device Manual 93