Appendix 7SV512 v1
C53000-G1176-C91 129
Table C.4 Reference Table for Functional Parameters 7SV512
1000 PARAMETERS
1100 POWERSYSTEM DATA
1105 In PRIMARY 1115 T-TRIP
min. 10 A min. 0.00 s
max. 50000 _______ max. 32.00 _______
1112 Ie/Iph
min. 0.10
max. 20.00 _______
1200 BREAKER FAILURE PROT.
1201 BREAK FAIL 1212 T2-CU RRENT
ON [ ] min. 0.00 s
OFF [ ] max. 32.00/ì _______
1202 I-BF 1213 T2-CB-AUX.
min. 0.05 I/In min. 0.00 s
max. 4.00 _______ max. 32.00/ì _______
1203 TRIP CRoff 1214 T3-CB-DEF.
YES [ ] min. 0.00 s
NO [ ] max. 32.00/ì _______
1204 TRIP 1POLE 1220 T-ENDFAULT
YES [ ] min. 0.00 s
NO [ ] max. 32.00/ì _______
1205 T1-1POLE 1221 BLOCK MON
min. 0.00 s YES [ ]
max. 32.00/ì _______ NO [ ]
1206 T1-3POLE 1222 T-BLOCKMON
min. 0.00 s min. 0.05 s
max. 32.00/ì _______ max. 32.00/ì _______
1211 T-TRIP-BB 1223 PLAUS 1POL
T1 + T2 [ ] RESIDUAL CURRENT [ ]
T2 [ ] NEG.SEQ. CURRENT [ ]