Technical data7SV512
V1
C53000---G1176---C9118
3.1.2 Electrical tests
Insulation tests
Standards: IEC 60255---5
--- High voltage test (routine test) 2 kV (rms); 50 Hz
except d.c. voltage supply input
--- High voltage test (routine test) 2.8 kV dc
only d.c. voltage supply input
--- Impulse voltage test (type test) 5 kV (peak); 1.2/50 s; 0.5 J; 3 positive
all circuits, class III and 3 negative shots at intervals of 5 s
EMC tests; immunity (type tests)
Standards: IEC 60255---6, IEC 60255---22 (product standards)
EN 50082---2 (generic standard)
VDE 0435 /part 303
--- High frequency 2.5 kV (peak); 1 MHz; =15 s; 400 shots/s;
IEC 60255---22---1, class III duration 2 s
--- Electrostatic discharge 4 kV/6 kV contact discharge; 8 kV air discharge;
IEC 60255---22---2 class III both polarities; 150 pF; R
i
= 330
and IEC 1000---4---2, class III
--- Radio-frequency electromagnetic field, 10 V/m; 27 MHz to 500 MHz
non-modulated; IEC 60255---22---3 (report) class
--- Radio-frequency electromagnetic field, 10 V/m; 80 MHz to 1000 MHz; 80 % AM; 1 kHz
amplitude modulated; IEC 1000---4---3, class
--- Radio-frequency electromagnetic field, pulse 10 V/m; 900 MHz; repetition frequency 200 Hz;
modulated; IEC 1000---4---3/ENV 50204, class duty cycle 50 %
--- Fast transients
IEC 60255---22---4 and IEC 1000---4---4, class 2 kV; 5/50 ns; 5 kHz; burst length 15 ms;
repetition rate 300 ms; both polarities; R
i
= 50 ;
duration 1 min
--- Conducted disturbances induced by
radio-frequency fields, amplitude modulated 10 V; 150 kHz to 80 MHz; 80 % AM; 1 kHz
IEC 1000---4---6, class III
--- Power frequency magnetic field
IEC 1000---4---8, class IV 30 A/m continuous; 300 A/m for 3 s; 50 Hz
IEC 60255---6 0.5 mT; 50 Hz
EMC tests; emission (type tests)
Standard: EN 50081---K (generic standard)
--- Conducted interference voltage, aux. voltage 150 kHz to 30 MHz
CISPR 22, EN 55022, class B
--- Interference field strength 30 MHz to 1000 MHz
CISPR 11, EN 55011, class A