Installation instructions7SV512
V1
52
C53000---G1176---C91
5.4.2 Programming the scope of functions --- address block 78
The available functions can be programmed as ex-
isting or not existing. Forsome functions it may also
be possible to select between multiple alternatives.
Functions which are configured as NON EXIST will
notbe processed in7SV512:There willbe noannun-
ciations and the associated setting parameters
(functions, limit values) will not be requested during
setting (Section 6.3). In contrast, switch-off of a
function means that the function will be processed,
that indication willappear (e.g. ”...switched off”)but
that the function will have no effect on the result of
the protective process (e.g. no command).
The following boxes show the possibilities for the
maximum scope of the device. In an actual case,
functions which are not available will not appear in
the display.
7 8 0 0 S C O P E O F
F U N C T I O N S
Beginning of the block ”scope of functions”
7 8 2 8 F A U L T R E C R D
E X I S T
N O N E X I S T
E X I S T
7 8 3 8 P O L E D I S C R P
N O N - E X I S T
E X I S T
7 8 6 9 L S A
N O N - E X I S T
E X I S T
7 8 8 5 P A R A M . C / O
N O N - E X I S T
The rated system frequency must comply with the setting under address 7899. If the system frequency is not
50 Hz, address 7899 must be changed.
7 8 9 9 F R E Q U E N C Y
f N 5 0 H z
f N 6 0 H z
Rated system frequency 50 Hz or 60 Hz