7SV512
Installation instructions
V1
59C53000---G1176---C91
Note as to Table 5.3: Annunciations with the function numbers below 100 are identical with those for binary
inputs. They represent the direct confirmation of the binary input and are available as longas the correspond-
ing binary input is energized. These direct confirmation functions are indicated by a leading ”>” sign.
Further information about annunciations see Section 6.4.
1 not allocated
5 >Time Synchro
6 >LED-reset
7 >Start FltRec
16 >CB Aux. L1
17 >CB Aux. L2
18 >CB Aux. L3
19 >CB Aux. 3p C
20 >CB Aux. 1p C
21 >Annunc. 1
22 >Annunc. 2
23 >Annunc. 3
24 >Annunc. 4
31 >B/F on
32 >B/F off
33 >Pole Dis. on
34 >Pole Dis.off
35 >Flt.Rec. on
36 >Flt.Rec. off
59 >ParamSelec.1
60 >ParamSelec.2
70 >Start
71 >Start N
72 >Trip
73 >Trip 3pole
74 >Trip L1
75 >Trip L2
76 >Trip L3
77 >B/F block
78 >CB defect
101 Dev.Operative
107 Flt.Rec.Trans
108 Fault.Rec.off
110 Param.Running
116 Param. Set A
117 Param. Set B
118 Param. Set C
119 Param. Set D
121 Failure 18V
122 Failure 15V
123 Failure 5V
124 Failure 0V
125 Failure RKA
151 Failure I
154 Failure Isymm
469 Device FltDet
470 Device Trip
471 BFP off
472 BFP-Pickup
473 BFP-Start
Binary output is not allocated to any output function
Synchronize internal real time clock
Reset LED indicators
Start fault recording from external command via binary input
Circuit breaker auxiliary contact L1 (L1 is closed)
Circuit breaker auxiliary contact L2 (L2 is closed)
Circuit breaker auxiliary contact L3 (L3 is closed)
Circuit breaker auxiliary contact all poles closed (series connection)
Circuit breaker auxiliary contact any pole closed (parallel connection)
User definable annunciation 1
User definable annunciation 2
User definable annunciation 3
User definable annunciation 4
Switch on breaker failure protection
Switch off breaker failure protection
Switch on pole discrepancy supervision
Switch off pole discrepancy supervision
Switch on fault recording function
Switch off fault recording function
Parameter set selection 1 (in connection with 060)
Parameter set selection 2 (in connection with 059)
General fault detection signal from feeder protection
Earth fault detection signal from feeder protection
General trip signal from feeder protection
Trip signal three-pole from feeder protection
Trip signal L1 from feeder protection
Trip signal L2 from feeder protection
Trip signal L3 from feeder protection
Block breaker failure protection
Circuit breaker defective (from circuit breaker monitor)
Relay operative
Fault record data are available or being transmitted
Fault recording switched off
Parameters are being set
Parameter Set A is activated
Parameter Set B is activated
Parameter Set C is activated
Parameter Set D is activated
Failure in 18 V internal dc supply
Failure in 15 V internal dc supply
Failure in 5 V internal dc supply
Failure in 0 V A/D converter
Failure in base input/output module
Failure supervision I (measured currents)
Failure supervision symmetry I
General fault detection signal
General trip signal
Breaker failure protection switched off
Breaker failure protection initiated (signal from feeder protection)
Breaker failure protection started
FNo Abbreviation Description
Table 5.3 Marshalling possibilities for signal relays and LEDs (Continued next page)