Modbus Data Formats
19
7. PCS = Programmable Current Scale. Ensure that scaling is compatible with the
expected register value; this provides maximum resolution and prevents register
overflow.
8. PnS = Programmable Neutral Current Scale. Ensure that scaling is compatible with
the expected register value; this provides maximum resolution and prevents register
overflow.
9. PPS = Programmable Power Scale. Ensure that scaling is compatible with the
expected register value; this provides maximum resolution and prevents register
overflow.
10. When it is read from that address the Low Order Word is fetched first.
11. These registers are duplicates of other UINT32 read-only registers differing only in
that the High Order Word is fetched first.
12. Digital output modes are: MW pulsing, MVAR pulsing, MVA pulsing, and digital
control. For digital output control information, refer to Digital Output Control in the
9200 Installation and Basic Setup Instructions.
13. The PML protocol is an ION compatible protocol used when other ION devices are
sharing a RS-485 network.
14. The RTS Delay parameter defines the delay between the 9200 becoming ready to
transmit data on the serial port, and the 9200 transmitting the data.
15. Number of seconds that a display is shown before scrolling to the next,
0 = no scrolling (disabled).
16. Number of seconds that a measurement value is held on the display before being
refreshed; limited to 1-6 seconds.
17. To use the Read-Write Control Map, it is recommended that your meter has firmware
version 202 or later. For detailed information, contact Technical Services.
Modbus Data Formats
To learn about Modbus data formats, refer to the 9200 Installation and Basic
Setup Instructions.
Exception Responses
To learn about Modbus exception responses, refer to the 9200 Installation
and Basic Setup Instructions.