Meter Settings
21
Meter Settings
These settings can be configured with the meter front panel or software.
String Description Range (Values) Default
MODE
Volts Mode
4W (4-Wire WYE)
dELt (Delta)
2W (Single Phase)
dEM (Demonstration)
3W (3-Wire WYE)
dELd (Delta Direct)
Delta
Direct
PTS
PT1 (Primary) 1 to (65.53 x 1000 LED) 480
PTS (Scaling)
*
1 (x 1); 1000 (x 1000) x1
PT2 (Secondary) 1 to (65.53 x 1000 LED) 480
CTS
CT1 (Primary) 1 to (65.53 x 1000 LED) 400
CT2 (Secondary) 1 to (65.53 x 1000 LED) 5
POLARITY
V1 Polarity
(Phase 1 voltage polarity)
n o r ( N o r m a l ) ; i n v ( I n v e r t e d ) N o r m a l
V2 Polarity
(Phase 2 voltage polarity)
nor (Normal); inv (Inverted) Normal
V3 Polarity
(Phase 3 voltage polarity)
nor (Normal); inv (Inverted) Normal
I1 Polarity
(Phase 1 current polarity)
nor (Normal); inv (Inverted) Normal
I2 Polarity
(Phase 2 current polarity)
nor (Normal; inv (Inverted) Normal
I3 Polarity
(Phase 3 current polarity)
nor (Normal); inv (Inverted) Normal
DEMAND
Demand Sub Interval 1 60 min 15
Number of Demand Periods 1 51
COMMUNICATIONS
Protocol
PML
**
; Mod (Modbus RTU)
Modbus
Baud Rate 1200, 2400, 4800, 9600, 19200 9600
Unit ID 1 247
100 plus
the last 2
digits of
the
Manufactu
rer ID #
RTS Delay 0 1000 milliseconds 20
tYPE
Pt1
Pt1
t
t
P
P
S
S
Pt2
Pt2
Ct1
Ct1
Ct2
Ct2
UPL1
UPL1
UPL2
UPL2
UPL3
UPL3
CPL1
CPL1
CPL2
CPL2
CPL3
CPL3
dPr
dPr
ndPr
Prot
b
b
A
A
d
d
u
u
n
n
d
d
u
u
rtS
rtS

Other manuals for Siemens 9200

Related product manuals