9200 Features Guide
22
Programmable Meter Language (PML) Protocol
* For the correct operation of a meter with the Megawatt option, PTS must be set to
“x1000.”
** ION compatible protocol for use with an WinPM.Net system and other Access meters.
Digital Outputs
† The units displayed on the front panel are Wh, VAh, and VARh with the actual values of
MWh, MVAh, and MVARh respectively.
MWh Rec. and MVARh Rec. are represented by a lit “minus” (negative value) LED.
†† In Ext 1 or Ext 2 mode, the digital outputs are reserved for Feature Packs or digital
control. For digital output control information, refer to the 9200 Installation and Basic
Setup Instructions.
MODBUS SCALING
Voltage Scale 0.001, 0.01, 0.1, 1, 10, 100, 1000 10
Current Scale 0.001, 0.01, 0.1, 1, 10, 100, 1000 10
Power Scale 0.001, 0.01, 0.1, 1, 10, 100, 1000 1
Neutral Scale 0.001, 0.01, 0.1, 1, 10, 100, 1000 10
DIGITAL OUTPUTS
Output Mode Digital #1
(M)Wh Del., (M)VAh, (M)VARh Del.,
(M)Wh Rec., (M)VARh Rec. See note.
†
Ext 1
††
, Ext 2
††
(M)Wh
†
Time Constant 1 (kT)
†††
0.1 – 999.9
(only 1 digit after the decimal pt.
permitted)
1.0
Output Mode Digital #2
(M)Wh Del., (M)VAh, (M)VARh Del.,
(M)Wh Rec., (M)VARh Rec. See note.
†
Ext 1
††
, Ext 2
††
(M)VARh
†
Time Constant 2 (kT)
†††
0.1 – 999.9
(only 1 digit after the decimal pt.
permitted)
1.0
Output Mode, Irda
(M)Wh Del., (M)VAh, (M)VARh Del.,
(M)Wh Rec., (M)VARh Rec. See note.
†
Ext 1
††
, Ext 2
††
Ext 1
††
Time Constant Irda (kT)
†††
0.1
– 999.9
(only 1 digit after the decimal pt. allowed)
1.0
DISPLAY
Display Scroll Time 0 – 30 seconds (0 = disable) 0
Display Refresh Period 1 – 6 seconds 2
SECURITY
Password 0 – 9999 0
String Description Range (Values) Default
PUS
PCS
PPS
PnS
out1
tc1
out2
tc2
otIr
tcIr
dS
r
c
dUPd
PSEt