9410 series Communications
Protocol Format
IPv4 0.0.0.0 to 255.255.255.255
IPv6 :: to FFFF:FFFF:FFFF:FFFF:FFFF:FFFF:FFFF:
FFFF
The double colon indicates that gaps are filled with
zeroes to make the IPv6 address the correct length
(32 hexadecimal numbers)
All meters ship from the factory with the IPv6 global address and IPv6 gateway
undefined (set to “::”). To communicate with the meter using IPv6 outside the local
network, you must configure these settings manually or use DHCP to assign the
addresses to the meter. Within the local network, you can use the meter’s IPv6 Link
Local address.
IP addresses and network port numbers
To specify a port for an outgoing IP address, append a colon (:) then the port number
to the end of the IP address. For IPv6 addresses, make sure the address is enclosed
in square brackets then append the port number. For example, to specify the default
port for ftp (port 21), the format of the address is as follows:
IPv4: 169.254.0.10:21
IPv6: [FE80::260:78FF:FE04:5943]:21
Configurable Ethernet settings
‘W’ indicates the setting can be configured (written) while ‘R’ indicates it is read-only.
NOTE: Some additional Ethernet settings are available in the Advanced Ethernet
menu in ION Setup and on the meter webpages.
Setting Display ION Setup Webpages
IPv4 address W W W
IPv4 Subnet mask W W W
IPv4 Default gateway W W W
IPv4 Assignment Mode
(DHCP/Stored)
W W W
IPv6 Assignment Mode
(DHCP/Stored)
W W W
Ethernet Device name R W W
Domain name R W W
IPv6 enabled
W W
IPv6 Link Local Address R R R
IPv6 global address R W W
IPv6 gateway R W W
Ethernet Rx timeout
W W
Modbus TCP timeout
W W
Modbus gateway
W
MAC address R R R
Ethernet primary DNS R W W
Ethernet secondary
DNS
R W W
54 7EN05-0336-03