Resets 9410 series
Parameter Description
Master Reset Clears all the cumulative and derived quantities from the meter
(including demand, peak demand, energy, revenue and test mode
parameters)
Clears meter event and waveform logs
Clears COMTRADE waveform records from the meter’s internal FTP
server
Clears the meter’s data logs
Peak Demand Reset Clears the peak demand values logged in the meter
Min/Max Reset Clears all accumulated maximum and minimum values stored in the
meter
Digital Input Count Reset Clears the digital input state change counters
Harmonics Min/Max Reset Clears all accumulated maximum and minimum harmonics values stored
in the meter
Disturbance Count Reset Clears the sag/swell event counter
EN50160 Reset Clears all EN50160 parameters and statistics accumulated in the meter
Option Modules Reset Restarts all option modules attached to the meter
Performing meter resets using ION Setup
You can perform meter resets on your meter using ION Setup.
Revenue-locked meters must be unlocked to perform resets that impact revenue data.
Meter resets clear the meter’s onboard data logs and other related information.
NOTICE
DATA LOSS
Failure to follow these instructions can result in data loss.
Ensure all important data from the device has been retrieved before performing a
reset.
1. Open the Setup Assistant for your meter.
2. Select the Verification screen.
3. Select Normal Mode and click Display.
4. Select the desired tab in the Normal Mode dialog box. Depending on the tab
selected, different resets are available.
Tab Reset available
Energy Master Reset
Rolling Demand Peak Reset
Master Reset
Volts, Amps and Power Master Reset
Conditional Energy Cnd Reset
Master Reset
Input Metering IM(n) Reset
NOTE: n is the input metering number, for example IM1.
Peak Reset
Master Reset
7EN05-0336-01 139