PMCM-9340D-0208 ACCESS 9340 and 9360 Meters
2/2008 Chapter 8—Logging
EN–101
Configure the Billing Log Logging Interval
The billing log can be configured to update every 10 to 1,440 minutes.
The default logging interval is 60 minutes. To set the logging interval
you can use WinPM.Net (see the WinPM.Net online Help for setup
details) or you can use the meter to write the logging interval to
register 3085 (see “Read and Write Registers” on page 36).
Table 8–6: Billing Log Register List
Description
Number of
Registers
Data Type➀ Register Number
Start Date/Time 3 D/T Current D/T
Real Energy In 4 MOD10L4 1700
Reactive Energy In 4 MOD10L4 1704
Real Energy Out 4 MOD10L4 1708
Reactive Energy Out 4 MOD10L4 1712
Apparent Energy Total 4 MOD10L4 1724
Total PF 1 INT16 1163
3P Real Power Demand 1 INT16 2151
3P Apparent Power Demand 1 INT16 2181
➀ Refer to Appendix A for more information about data types.