ACCESS 9340 and 9360 Meters PMCM-9340D-0208
Appendix A—Meter Register List 2/2008
EN–164
Base +14
Lower Limit
Analog Value
0 – ±327
Lower limit of the analog input value. Default
value based on I/O Point Type.
Base +15
Upper Limit
Analog Value
0 – ±327
Upper limit of the analog input value. Default
value based on I/O Point Type.
Base +16
Lower Limit
Register Value
0 – ±32,767
Lower limit of the register value associated with
the lower limit of the analog input value.
Base +17
Upper Limit
Register Value
0 – ±32,767
Upper limit of the register value associated with
the upper limit of the analog input value.
Base +18 Reserved Reserved for future development
Base +19 User Gain Adjustment 0.0001 8,000 – 12,000
Analog input user gain adjustment in 100ths of a
percent. Default = 10,000.
Base +20 User Offset Adjustment 0 – ±30,000
Analog input user offset adjustment in Bits of
digital resolution. Default = 0.
Base +21 Reserved Reserved for future development
Base +22
IO Point Diagnostic
Bitmap
0x0000 – 0x0007
0 = OK, 1 = Error
Bit 00 = I/O Point diagnostic summary
Bit 01 = Configuration invalid – default value
used
Base +23
Lower Limit
Digital Value
0 – ±32,767
Lower limit of the digital value associated with
the lower limit of the analog input value. Value
based on I/O Point Type.
Base +24
Upper Limit
Digital Value
0 – ±32,767
Upper limit of the digital value associated with
the upper limit of the analog input value. Value
based on I/O Point Type.
Base +25 Present Raw Value 0 – ±32,767 Raw digital value read from analog input.
Base +26 Present Scaled Value 0 – ±32,767
Raw value corrected by calibration gain and
offset adjustments and scaled based on range
of register values.
Base +27 Calibration Offset 0 – ±32,767 Analog input offset adjustment
Base +28
Calibration Gain
(Voltage)
0.0001 8,000 – 12,000 Analog input gain adjustment
Base +29
Calibration Gain
(Current)
0.0001 8,000 – 12,000 Analog input gain adjustment
Table A4: Registers for Inputs and Outputs