© 2008 Siemens Energy & Automation, Inc. All Rights Reserved
ACCESS 9340 and 9360 Meters PMCM-9340D-0208
Appendix C—EN50160 Evaluation 2/2008
EN–224
Table C–3: Values of individual harmonic voltages at the supply terminals for orders up to
25 in % of nominal voltage
Odd Harmonics
Even Harmonics
Not Multiples of 3 Multiples of 3
Order h
Relative
Voltage
Order h
Relative
Voltage
Order h
Relative
Voltage
56%35%22%
75%91.5%41%
11 3.5% 15 0.5% 6...24 0.5%
13 3% 21 0.5%
17 2%
19 1.5%
23 1.5%
25
NOTE: No values are given for harmonics of order higher than 25, as they are usually
small, but largely unpredictable because of resonance effects.