59 / 92
Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en
Building Technologies Functions and control 2018-12-05
4.3.2 Changeover of acting direction
Acting direction
OFF
1)
Direct acting
positioning signal Y or Z
ON
1)
Reverse acting
positioning signal Y or Z
1)
Factory setting: All switches set to OFF
· With valves whose stem is extended in the fully closed position, "direct acting"
means that the valve is fully closed (0%) when positioning signal Y = 0 V resp.
Z = 0 Ω. This applies to all Siemens valves according to "Equipment
combinations" (page 14).
· With valves whose stem is retracted in the fully closed position, "direct acting"
means that the valve is fully open (100%) when positioning signal Y = 0 V resp.
Z = 0 Ω.
Direct acting Reverse acting
Positioning signal Y: DC 0…10 V
4…20 mA
Positioning signal Z: 0...1000 W
Y, Z Positioning signal
V Volumetric flow
Acting direction: Direct
Acting direction: Reverse
Reverse acting Direct acting
Positioning signal Y: DC 0…10 V
4…20 mA
Positioning signal Z: 0...1000 W
DIL switches
Selecting the acting
direction
SAX61.03
SAV61.00
SAY61P03
SAX61P03
SAV61P00

Table of Contents