Commissioning / Operation / Maintenance AddFEM
5-48
AddFEM
C79000–G8076–C900–03
The FEM_AI has the following input parameters:
Table 5-7 Input parameters of the FEM_AI
Parameter Comment Data type Visible Default
G_ADR_1A Geografical Address Interface A Unit 1 INT Yes 0
G_ADR_1B Geografical Address Interface B Unit 1 INT Yes 0
G_ADR_2A Geografical Address Interface A Unit 2 INT Yes 0
G_ADR_2B Geografical Address Interface B Unit 2 INT Yes 0
MASTER Set Master (no failure state)
0 = Unit 1 is master
1 = Unit 2 is master
BOOL Yes 0
FEF_EN 1 = Front End Function enabled BOOL Yes 0
DBNRFEF Data Block Number FEF Input Parameter INT Yes 0
AI1_HRG Analog Input 1 High Range REAL Yes 100.0
AI1_LRG Analog Input 1 Low Range REAL Yes –100.0
AI1_SIM Simulation Value Analog Input 1 REAL No 0.0
SIMUAI1 1 = Simulation on BOOL No 0
AI2_HRG Analog Input 2 High Range REAL Yes 100.0
AI2_LRG Analog Input 2 Low Range REAL Yes –100.0
AI2_SIM Simulation Value Analog Input 2 REAL No 0.0
SIMUAI2 1 = Simulation on BOOL No 0
AI3_HRG Analog Input 3 High Range REAL Yes 100.0
AI3_LRG Analog Input 3 Low Range REAL Yes –100.0
AI3_SIM Simulation Value Analog Input 3 REAL No 0.0
SIMUAI3 1 = Simulation on BOOL No 0
AI4_HRG Analog Input 4 High Range REAL Yes 100.0
AI4_LRG Analog Input 4 Low Range REAL Yes –100.0
AI4_SIM Simulation Value Analog Input 4 REAL No 0.0
SIMUAI4 1 = Simulation on BOOL No 0
AI5_HRG Analog Input 5 High Range REAL Yes 100.0
AI5_LRG Analog Input 5 Low Range REAL Yes –100.0
AI5_SIM Simulation Value Analog Input 5 REAL No 0.0
SIMUAI5 1 = Simulation on BOOL No 0
AI6_HRG Analog Input 6 High Range REAL Yes 100.0
AI6_LRG Analog Input 6 Low Range REAL Yes –100.0
AI6_SIM Simulation Value Analog Input 6 REAL No 0.0
SIMUAI6 1 = Simulation on BOOL No 0
AI7_HRG Analog Input 7 High Range REAL Yes 100.0
AI7_LRG analog Input 7 Low Range REAL Yes –100.0
AI7_SIM Simulation Value Analog Input 7 REAL No 0.0
SIMUAI7 1 = Simulation on BOOL No 0
AI8_HRG Analog Input 8 High Range REAL Yes 100.0
AI8_LRG Analog Input 8 Low Range REAL Yes –100.0
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com