Siemens Building Technologies CM2N3204E / 1.1999
Landis & Staefa Division 15/20
Wiring diagram 6:
measuring part with CO
2
/VOC sensor for demand controlled
ventilation
SP
G
3204A07
B7
G0
N1
SN
MB2
M
AC 24 V
M
B1
Z
B1
G
CO
2
/VOC CO
2
N1 Controller RWI65.02
N2 RVL55 with plug-in module AZY55.60
B1 Room or extract air temperature detector QAA24/QAM22...
B2 Supply air temperature detector QAM22...
B3 Outside detector QAM22.../QAC22
B4 Frost detector QAD22/QAE21.6
B5 Frost detector QAF63.2/QAF63.6
B6 Extract air temperature detector QAM22...
B7 CO
2
/VOC sensor QPA62...
R1 Remote setting unit FZA61.11
R2 Room unit QAA26 or setting unit FZA21.21
Wiring diagram 7:
control part with regulating units for heating, cooling and HR
SP
G
G0 Y10
GY
G0
Y20 Y30
SN
N1
Y1 Y2 Y3
3204A05
AC 24 V
GGGG0G0G0
GY
G0
GY
G0
N1 Controller RWI65.02
Y1 Regulating unit for heating
Y2 Regulating unit for cooling
Y3 Regulating unit for HR/recirculated air dampers
Wiring diagram 8:
GE
E1 E2
E3
E4 E5
E6
Q44
Q13 Q33
Q34
3204A06
T
p
F91
L
H1
K3 K4
N1
AC 230 V
AC 24 V
F3
F3
Auto
0
I
II
E7 E8
Q24
F2
Q14
F1
K2
K1
S1
G
G0
F2F1
N
SP
SN
K4
K3
F4
F4
N1 Controller RWI65.02
F1...F4 Overload relay contact
H1 Auxiliary unit for common fault signal
K1 Motor contactor for hot water pump or contactor for electric heater battery
K2 Motor contactor for chilled water circulator or chiller
K3 Motor contactor for fan speed I
K4 Motor contactor for fan speed II
Legend for wiring
diagrams 1 to 6
Connections on the
control side
Connections on the
control and
supervision side