7SR220 Settings Guide
Unrestricted ©2018 Siemens Protection Devices Limited Page 25 of 107
3.4.5.3. 51G-3
Description Range Default
Gn 51G-3 Element
Selects whether the 51G-3 IDMTL measured Earth Fault
element is enabled
Disabled, Enabled Disabled
Gn 51G-3 Dir. Control
Selects whether 51G-3 element is non-directional, forward or
reverse
Non-Dir, Forward, Reverse Non-Dir
Gn 51G-3 Setting
Pickup level
0.005, 0.006 ... 0.995, 1 0.5 xIn
Gn 51G-3 Char
Selects characteristic curve to be IEC or ANSI IDMTL or DTL
DTL, IEC-NI, IEC-VI, IEC-EI, IEC-
LTI, ANSI-MI, ANSI-VI, ANSI-EI
IEC-NI
Gn 51G-3 Time Mult (IEC/ANSI)
Time multiplier (applicable to IEC and ANSI curves but not
DTL selection)
0.025, 0.03 ... 1.595, 1.6 , 1.7 ...
4.9, 5, 6 ... 100
1
Gn 51G-3 Delay (DTL)
Delay (applicable only when DTL is selected for characteristic)
0, 0.01 ... 19.99, 20 5 s
Gn 51G-3 Min Operate Time
Minimum operate time of element.
0, 0.01 ... 19.99, 20 0 s
Gn 51G-3 Follower DTL
Additional definite time added after characteristic time
0, 0.01 ... 19.99, 20 0 s
Gn 51G-3 Reset
Selects between an ANSI decaying reset characteristic or DTL
reset
(ANSI) Decaying, 0 ... 59, 60 0 s
Gn 51G-3 VTS Action
Selects whether 51G-3 element is blocked or made non-
directional when VTS operates
Off, Inhibit, Non-Dir Off
Gn 51G-3 Inrush Action
Selects if the 51G-3 element is blocked from operating when
2nd Harmonic Inrush Detector operates
Off, Inhibit Off
3.4.5.4. 51G-4
Description Range Default
Gn 51G-4 Element
Selects whether the 51G-4 IDMTL measured Earth Fault
element is enabled
Disabled, Enabled Disabled
Gn 51G-4 Dir. Control
Selects whether 51G-4 element is non-directional, forward or
reverse
Non-Dir, Forward, Reverse Non-Dir
Gn 51G-4 Setting
Pickup level
0.005, 0.006 ... 0.995, 1 0.5 xIn
Gn 51G-4 Char
Selects characteristic curve to be IEC or ANSI IDMTL or DTL
DTL, IEC-NI, IEC-VI, IEC-EI, IEC-
LTI, ANSI-MI, ANSI-VI, ANSI-EI
IEC-NI
Gn 51G-4 Time Mult (IEC/ANSI)
Time multiplier (applicable to IEC and ANSI curves but not
DTL selection)
0.025, 0.03 ... 1.595, 1.6 , 1.7 ...
4.9, 5, 6 ... 100
1
Gn 51G-4 Delay (DTL)
Delay (applicable only when DTL is selected for characteristic)
0, 0.01 ... 19.99, 20 5 s
Gn 51G-4 Min Operate Time
Minimum operate time of element.
0, 0.01 ... 19.99, 20 0 s
Gn 51G-4 Follower DTL
Additional definite time added after characteristic time
0, 0.01 ... 19.99, 20 0 s