EasyManua.ls Logo

Siemens Argus 7SR22 - Page 239

Siemens Argus 7SR22
644 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7SR220 Settings Guide
Unrestricted Page 34 of 107 © 2013 Siemens Protection Devices Limited
Description Range Default
Gn 27/59 U/V Guard Setting
Selects voltage level below which the guard element is
applied.
1, 1.5 ... 199.5, 200 5 V
3.5.2. 27/59-1
Description Range Default
Gn 27/59-1 Element
Selects whether the Under/Over voltage element stage 1 is
enabled
Disabled, Enabled Disabled
Gn 27/59-1 Operation
Selects between Undervoltage and Overvoltage pickup for this
element
Under, Over Over
Gn 27/59-1 Setting
Under or over voltage pickup level
5, 5.5 ... 199.5, 200 80 V
Gn 27/59-1 Hysteresis
Sets the pickup to dropoff thresholds e.g. 3% on Overlevel
picks up above pickup setting and drops off below 97% of
setting, 3% on Underlevel picks up below setting and drops off
above 103% of setting
0, 0.1 ... 79.9, 80 3 %
Gn 27/59-1 Delay
Sets operate delay time
0, 0.01 ... 14300, 14400 0.1 s
Gn 27/59-1 U/V Guarded
Selects whether U/V Guard element can block the operation of
this element
No, Yes No
Gn 27/59-1 VTS Inhibit
Selects whether element is blocked or not when VTS operates
No, Yes No
Gn 27/59-1 O/P Phases
Selects whether element operates for any phase picked up or
only when all phases are picked up
Any, All Any
3.5.3. 27/59-2
Description Range Default
Gn 27/59-2 Element
Selects whether the Under/Over voltage element stage 2 is
enabled
Disabled, Enabled Disabled
Gn 27/59-2 Operation
Selects between Undervoltage and Overvoltage pickup for this
element
Under, Over Over
Gn 27/59-2 Setting
Under or over voltage pickup level
5, 5.5 ... 199.5, 200 80 V
Gn 27/59-2 Hysteresis
Sets the pickup to dropoff thresholds e.g. 3% on Overlevel
picks up above pickup setting and drops off below 97% of
setting, 3% on Underlevel picks up below setting and drops off
above 103% of setting
0, 0.1 ... 79.9, 80 3 %
Gn 27/59-2 Delay
Sets operate delay time
0, 0.01 ... 14300, 14400 0.1 s
Gn 27/59-2 U/V Guarded
Selects whether U/V Guard element can block the operation of
this element
No, Yes No
Gn 27/59-2 VTS Inhibit
Selects whether element is blocked or not when VTS operates
No, Yes No

Table of Contents