7SR220 Settings Guide
Unrestricted Page 70 of 107 © 2013 Siemens Protection Devices Limited
Description Range Default
Select Group 1
Switches active setting group to group 1
Combination of ( BI1, BI2, BI3, BI4,
BI5, BI6, BI7, BI8, BI9, BI10, BI11,
BI12, BI13, V1, V2, V3, V4, V5, V6,
V7, V8, V9, V10, V11, V12, V13,
V14, V15, V16 )
----------------------
-------
Reset Energy Meters Combination of ( BI1, BI2, BI3, BI4,
BI5, BI6, BI7, BI8, BI9, BI10, BI11,
BI12, BI13, V1, V2, V3, V4, V5, V6,
V7, V8, V9, V10, V11, V12, V13,
V14, V15, V16 )
----------------------
-------
Select Group 2
Switches active setting group to group 2
Combination of ( BI1, BI2, BI3, BI4,
BI5, BI6, BI7, BI8, BI9, BI10, BI11,
BI12, BI13, V1, V2, V3, V4, V5, V6,
V7, V8, V9, V10, V11, V12, V13,
V14, V15, V16 )
----------------------
-------
Select Group 3
Switches active setting group to group 3
Combination of ( BI1, BI2, BI3, BI4,
BI5, BI6, BI7, BI8, BI9, BI10, BI11,
BI12, BI13, V1, V2, V3, V4, V5, V6,
V7, V8, V9, V10, V11, V12, V13,
V14, V15, V16 )
----------------------
-------
Select Group 4
Switches active setting group to group 4
Combination of ( BI1, BI2, BI3, BI4,
BI5, BI6, BI7, BI8, BI9, BI10, BI11,
BI12, BI13, V1, V2, V3, V4, V5, V6,
V7, V8, V9, V10, V11, V12, V13,
V14, V15, V16 )
----------------------
-------
Select Group 5
Switches active setting group to group 5
Combination of ( BI1, BI2, BI3, BI4,
BI5, BI6, BI7, BI8, BI9, BI10, BI11,
BI12, BI13, V1, V2, V3, V4, V5, V6,
V7, V8, V9, V10, V11, V12, V13,
V14, V15, V16 )
----------------------
-------
Select Group 6
Switches active setting group to group 6
Combination of ( BI1, BI2, BI3, BI4,
BI5, BI6, BI7, BI8, BI9, BI10, BI11,
BI12, BI13, V1, V2, V3, V4, V5, V6,
V7, V8, V9, V10, V11, V12, V13,
V14, V15, V16 )
----------------------
-------
Select Group 7
Switches active setting group to group 7
Combination of ( BI1, BI2, BI3, BI4,
BI5, BI6, BI7, BI8, BI9, BI10, BI11,
BI12, BI13, V1, V2, V3, V4, V5, V6,
V7, V8, V9, V10, V11, V12, V13,
V14, V15, V16 )
----------------------
-------
Select Group 8
Switches active setting group to group 8
Combination of ( BI1, BI2, BI3, BI4,
BI5, BI6, BI7, BI8, BI9, BI10, BI11,
BI12, BI13, V1, V2, V3, V4, V5, V6,
V7, V8, V9, V10, V11, V12, V13,
V14, V15, V16 )
----------------------
-------
Out Of Service Mode
Selects which inputs will put the relay into Out Of Service
Mode
Combination of ( BI1, BI2, BI3, BI4,
BI5, BI6, BI7, BI8, BI9, BI10, BI11,
BI12, BI13, V1, V2, V3, V4, V5, V6,
V7, V8, V9, V10, V11, V12, V13,
V14, V15, V16 )
----------------------
-------
Local Mode
Selects which inputs will put the relay into Local Mode
Combination of ( BI1, BI2, BI3, BI4,
BI5, BI6, BI7, BI8, BI9, BI10, BI11,
BI12, BI13, V1, V2, V3, V4, V5, V6,
V7, V8, V9, V10, V11, V12, V13,
V14, V15, V16 )
----------------------
-------
Remote Mode
Selects which inputs will put the relay into Remote Mode
Combination of ( BI1, BI2, BI3, BI4,
BI5, BI6, BI7, BI8, BI9, BI10, BI11,
BI12, BI13, V1, V2, V3, V4, V5, V6,
V7, V8, V9, V10, V11, V12, V13,
V14, V15, V16 )
----------------------
-------
Local Or Remote Mode
Selects which inputs will put the relay into Local Or Remote
Mode
Combination of ( BI1, BI2, BI3, BI4,
BI5, BI6, BI7, BI8, BI9, BI10, BI11,
BI12, BI13, V1, V2, V3, V4, V5, V6,
V7, V8, V9, V10, V11, V12, V13,
V14, V15, V16 )
----------------------
-------