EasyManua.ls Logo

Siemens Argus 7SR22 - Page 354

Siemens Argus 7SR22
644 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7SR21 & 7SR22 Performance Specification
Unrestricted Page 42 of 68 © 2013 Siemens Protection Devices Limited
2.15.3 Operate and Reset Time
Attribute Value
Starter operate time (³ 2 xIs) 20 ms, ± 20 ms
t
op
Operate time
char = IEC-NI,
IEC-VI,
IEC-EI,
IEC-LTI
[ ]
Tm
K
t
Is
I
op
´
-
=
1
a
, ± 5 % or ± 30 ms,
for char = IEC-NI : K = 0.14, a = 0.02
IEC-VI : K = 13.5, a = 1.0
IEC-EI : K = 80.0, a = 2.0
IEC-LTI : K = 120.0, a = 1.0
char = ANSI-MI,
ANSI-VI,
ANSI-EI
[ ]
TmB
A
t
P
Is
I
op
´
ú
ú
û
ù
ê
ê
ë
é
+
-
=
1
, ± 5 % or ± 30 ms,
for char = ANSI-MI : A = 0.0515, B = 0.114, P = 0.02
ANSI-VI : A = 19.61, B = 0.491, P = 2.0
ANSI-EI : A = 28.2, B = 0.1217, P = 2.0
char = DTL
t
d
, ± 1 % or ± 20 ms
Reset time
ANSI DECAYING
[ ]
Tm
R
t
Is
I
res
´
-
=
1
2
, ± 5 % or ± 30 ms,
for char = ANSI-MI : R = 4.85
ANSI-VI : R = 21.6
ANSI-EI : R = 29.1
t
res
t
res
, ± 1 % or ± 20 ms
Repeatability
± 1 % or ± 20 ms
Overshoot time < 40 ms
Disengaging time < 50 ms
Figure 2-2 shows the operate times for the four IEC IDMTL curves with a time multiplier of 1. Figure 2-3 and
Figure 2-4 show the ANSI operate and reset curves respectively. These operate times apply to non-directional
characteristics. Where directional control is applied then the directional element operate time should be added to
give total maximum operating time.

Table of Contents

Other manuals for Siemens Argus 7SR22

Related product manuals