Address Description Format Mult Description
30195 I Phase B Max FP_32BITS_3DP 1.000000 Ib Max Demand
30197 I Phase C Max FP_32BITS_3DP 1.000000 Ic Max Demand
30199 P 3P Max FP_32BITS_3DP 0.000001 Power Max Demand
30201 Q 3P Max FP_32BITS_3DP 0.000001 VARs Max Demand
30203 Ig Max FP_32BITS_3DP 1.000000 Ig Max Demand
30207 Isef Primary FP_32BITS_3DP 1.000000 Isef A
30209 Isef Secondary FP_32BITS_3DP 1.000000 Isef A
30211 Isef Nominal FP_32BITS_3DP 1.000000 Isef xInom
30213 Fault Distance Percent FP_32BITS_3DP 1.000000 Fault Distance Percent
30215 Fault Reactance FP_32BITS_3DP 1.000000 Fault Reactance
30241 CB Total Trip Count UINT32 1.000000 CB Total Trip Count
30243 CB Delta Trip Count UINT32 1.000000 CB Delta Trip Count
30245 CB Count To AR Block UINT32 1.000000 CB Count to AR Block
30247 CB Frequent Ops Count UINT32 1.000000 CB Frequent Ops Count
30293 Bus Freq FP_32BITS_3DP 1.000000 Vx Frequency
30295 Phase Diff FP_32BITS_3DP 1.000000 25 Phase Diff
30297 Slip Freq FP_32BITS_3DP 1.000000 25 Slip Freq
30299 Voltage Diff FP_32BITS_3DP 1.000000 25 Voltage Diff
30301 Ia Last Trip FP_32BITS_3DP 1.000000 Ia Fault
30303 Ib Last Trip FP_32BITS_3DP 1.000000 Ib Fault
30305 Ic Last Trip FP_32BITS_3DP 1.000000 Ic Fault
30307 Va Last Trip FP_32BITS_3DP 1.000000 Va Fault
30309 Vb Last Trip FP_32BITS_3DP 1.000000 Vb Fault
30311 Vc Last Trip FP_32BITS_3DP 1.000000 Vc Fault
30313 In Last Trip FP_32BITS_3DP 1.000000 In Fault
30315 Ig Last Trip FP_32BITS_3DP 1.000000 Ig Fault
30317 Isef Last Trip FP_32BITS_3DP 1.000000 Isef Fault
30319 V Phase A Max FP_32BITS_3DP 1.000000 Va Max Demand
30321 V Phase B Max FP_32BITS_3DP 1.000000 Vb Max Demand
30323 V Phase C Max FP_32BITS_3DP 1.000000 Vc Max Demand
30325 V Phase AB Max FP_32BITS_3DP 1.000000 Vab Max Demand
30327 V Phase BC Max FP_32BITS_3DP 1.000000 Vbc Max Demand
30329 V Phase CA Max FP_32BITS_3DP 1.000000 Vca Max Demand
30331 CB Ph A Trip Count UINT32 1.000000 CB Phase A Trip Count
30333 CB Ph B Trip Count UINT32 1.000000 CB Phase B Trip Count
30335 CB Ph C Trip Count UINT32 1.000000 CB Phase C Trip Count
30337 CB E/F Trip Count UINT32 1.000000 CB EF Trip Count
30341 LED1-n BITSTRING 0.000000 Led 1-16 status
30342 LED1-n BITSTRING 0.000000 Led 17-32 status
30343 INP1-n BITSTRING 0.000000 Input 1-16 status
30344 INP1-n BITSTRING 0.000000 Input 17-32 status
30345 OUT1-n BITSTRING 0.000000 Output 1-16 status
30346 OUT1-n BITSTRING 0.000000 Output 17-32 status
30347 VRT1-n BITSTRING 0.000000 Virtual 1-16 status
30348 VRT1-n BITSTRING 0.000000 Virtual 17-32 status
30349 EQN1-n BITSTRING 0.000000 Equation 1-16 status
30350 EQN1-n BITSTRING 0.000000 Equation 17-32 status
30352 Fault Distance Perunit FP_32BITS_3DP 1.000000 Fault Distance Perunit