EasyManua.ls Logo

Siemens Argus 7SR22 - Page 549

Siemens Argus 7SR22
644 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7SR210 & 7SR220 Commissioning & Maintenance Guide
© 2013 Siemens Protection Devices Limited Page 37 of 82
Calculated Timing values in seconds for TM =1.0
Curve 2 xIs 5 xIs
IEC-NI 10.03 4.28
IEC-VI 13.50 3.38
IEC-EI 26.67 3.33
IEC-LTI 120.00 30.00
ANSI-MI 3.80 1.69
ANSI-VI 7.03 1.31
ANSI-EI 9.52 1.30
Note that the operate time may be subject to the Minimum op time setting for the element and/or may have a
Follower DTL applied.
If VTS action is set to BLOCK, this option should be tested. Apply balanced voltage and current. Reduce a-phase
voltage to cause a VTS condition. Increase a-phase current and check that the element does not operate.
If VTS action is set to Non-Directional, this option should be tested..Apply balanced voltage and current. Reduce
a-phase voltage to cause a VTS condition. Increase a-phase current and check that the element operates at its
normal setting. Reverse the voltage phase direction whilst checking that the element does not reset.
1.1.1.1 Element Blocking
The Sensitive Earth Fault elements can be blocked by Binary Input Inhibit and VT Supervision. The Characteristic
can be made non-directional by VT Supervision. This functionality should be checked.
Element BI Inhibits VTS action
51SEF-1
51SEF-2
51SEF-3
51SEF-4
50SEF-1
50SEF-2
50SEF-3
50SEF-4

Table of Contents

Other manuals for Siemens Argus 7SR22

Related product manuals