Installation
Power supply
-
mains voltage connection
6
51 |
118
Building Technologies
A6V10211100_f_en_
--
Fire Safety
2015
-
-
15
Determining the battery type
Determine the battery type on the basis of the calculated battery capacity (see
table).
Designation Type Capacitance Order number
Battery (12 V, 7 Ah, VDS) FA2003-A1 7 Ah A5Q00019353
Battery (12 V, 12 Ah, VDS) FA2004-A1 12 Ah A5Q00019354
Battery (12 V, 17 Ah, VDS) FA2005-A1 17 Ah A5Q00019677
Battery (12 V, 26 Ah, VDS) FA2006-A1 26 Ah A5Q00019356
Table 2: Permitted batteries
NOTICE
Hardware damage
Due to CE conformity only UL94
-
V2 batteries may be used.
Notes
To achieve the system voltage of 24 V, two batteries must always be
connected in series.
Batteries are not included in the scope of supply of the stations and must be
ordered separately.
The battery capacity determines the charging current. The charging current
must be taken into account when calculating the power supply.
The dimensions of the batteries are needed to determine the housing type.
Restriction of the battery dimensions
With greater battery capacities, the additional empty housing (Standard) should
be used with a 150 W power supply.