Installation
C
-
NET detector line
6
63 |
118
Building Technologies
A6V10211100_f_en_
--
Fire Safety
2015
-
-
15
The connection terminals for the C-NET are on the periphery board.
Figure 24: Position of C-NET connection terminal on the periphery board
Max. 126 C-NET devices are permitted on the C-NET connection (block of 4
terminals).
The C-NET devices can be distributed on the loop (max. 126 devices) or on
two stubs (max. 32 devices per stub).
Loop connection example
Max. 126 line devices
Figure 25: C-NET loop circuit
Alternatively, the connection of two stubs instead of one loop is possible
Stub connection example
Max. 32 line devices per stub
Total of max. 64 line devices per line connection (4 terminals)
Figure 26: C-NET stub circuit
X11
1
2
3
4
+
-
+
-
C
Cerbe rus
TM
1
2
3
4
+
-
+
-
C
Cerberus
TM