Commissioning
Restart the station
10
94 | 118
Building Technologies
A6V10211100_f_en_
--
Fire Safety
2015
-
-
15
10.7 Restart the station
The co
nfiguration of the
'
Station
' remains the same.
There are the following ways in which to restart the 'Station':
Via the menu on the display
PMI & mainboard FCM2004 and FCM2027: With the 'S32' button
CPU card: With the 'S8' button
Via the menu on the display
If you are using two CPU cards, you must perform the following procedure once
for each CPU card.
1. Press <MENU>.
The PIN input dialog is displayed.
2. Enter a valid PIN and confirm with <ok>.
The 'User successfully logged in' message is displayed.
The main menu is displayed.
3. Select the 'Topology' > 'Hardware tree' > 'Station' menu items.
The elements of the 'Station' are listed.
4. Select module 101 or module 102 'CPU (FCC2001/06)'.
5. Press the 'MoreOptions' softkey and select 'Execute commands'.
6. Select the 'Reset module' command.
The 'Station' shuts down.
The 'Station' is switched off for several seconds.
The 'Station' restarts.
PMI & mainboard FCM2004 and FCM2027
ϖ Switches S38-1 and S38-2 are set to the 'OFF' position on the PMI &
mainboard FCM2004.
κ On the PCB of the operating unit, press and hold down the 'S32' button for
<2 s.
The 'Station' shuts down.
The 'Station' is switched off for several seconds.
The 'Station' restarts.