Status
Free Cooling LED
Sensor LED
DAC LED
Humidity sensor error
-
Yellow On
-
CO
2
sensor error
-
LED Off
-
Air temperature failure/fault
-
Red On
-
Excess outdoor air
-
Red Blinking
-
Damper working ok
-
-
Green On
Damper stalled
-
-
Red On
Damper slippage
-
-
Red Blinking
Actuator alarm is reported
-
-
Fast Red Blinking
Terminal ACT-FB is configured
but no available feedback
signal (under-range or over-
range)
-
-
LED Off
NOTICE
If different faulty events occur at the same time, sensor/DAC LED lights up following the
priority below: Red (Fast Blinking) -> Red (On, Steady) -> Red (Blinking) -> Yellow -> Off ->
Green. For example, if there is a humidity sensor error and air temperature failure at the
same time, the sensor LED turns red rather than yellow.
After the Economizer controller enters the running state, it may take one minute for
peripheral devices to complete initialization. Before that, LED indication might be unstable.
Type
Order number
Description
POL224.00
S55392-C202-A100
POL224.00 Title24 Economizer Controller
POL224.05
1)
S55392-C203-A100
POL224.05 Title24 Economizer Controller
without housing
POL224.00/M24
1)
S55392-C202-B100
POL224.00/M24 Title24 Economizer
Controller Bulk Pack 24
1
Without individual package. 24 items per pack.