6.2 Modbus components
General rule Devices that can be connected to Modbus master Interface
Device Description Address Note
POS9.1515 IO extension 41
QBM97 (1) Air pressure sensor # 1 40 DIP switch setting required
QBM97 (2) Air pressure sensor # 2 42 DIP switch setting required
FanSu EBM Papst supply air fan 1 Configuration with EBM Papst tool required.
Must be used together with EBM Papst
exhaust air fan
FanEh EBM Papst exhaust air fan 2 Configuration with EBM Papst tool required.
Must be used together with EBM Papst supply
air fan
Protocol parameters
Baud rate 19200
Parity Even
Stop bits 1
Communication monitoring
Communication with the slave devices is constantly monitored. The monitoring is
activated as soon as the device is selected (basic configuration).
If the communication with the device cannot be established or gets lost, individual
alarm is triggered:
B-Alarm "3005: I/O extension module, Modbus communication error"
B-Alarm "3011: Duct pressure sensor, Modbus communication error"
Configurable "3012: Supply air fan, Modbus communication error"
Configurable "3013: Exhaust air fan, Modbus communication error"
An adjustable delay time to avoid false alarms due to short disturbances can be
configured.
Available parameters
Actual values BA-object R/RW Note
Delay for
communication error
DlyComErr, PINTVAL, 80 RW The alarm is triggered as soon the set
time has elapsed.
Default = 120s
Engineering of communicative devices
Modbus components
6
146 | 170 A6V10733786_en_c