Program blocks
5.4 IF_CONF: SDT for the configuration data of the CP
CP 1243-7 LTE
Operating Instructions, 04/2017, C79000-G8976-C381-03
115
In STEP 7, the corresponding data is located in the "Partner stations" parameter area.".
This field is only used when the telecontrol server is addressed with a name that can be
resolved by DNS or when the IP address is to stored as a string.
Table 5- 5 IF_CONF_TCS_Name
ID of the parameter field
Length UINT Length of the parameter field in bytes: 266
Validity (1, 2) - see above (general parameters)
TcsName
STRING [254] Name of the telecontrol server that can be resolved by
DNS or IP address as string
Port of the telecontrol server
Rank UINT Priority of the server [1, 2]
1 = first telecontrol server,
2 = second telecontrol server (second server not relevant)
In STEP 7, the corresponding data can be found in the parameter area "Mobile wireless
communications settings" > "Services and settings".
Table 5- 6 IF_CONF_SMS_Provider
ID of the parameter field
Length of the parameter field in bytes: 28
Validity (1, 2) - see above (general parameters)
SMSProvider STRING [20] Subscriber number of the SMS center (SMSC) of the
mobile wireless network provider with which the mobile
wireless contract was signed for this station.
In STEP 7, the PIN can be found in the parameter area "Mobile wireless communications
settings" > "Services and settings".
Table 5- 7 IF_CONF_PIN
ID of the parameter field
Length of the parameter field in bytes: 16
Validity (1, 2) - see above (general parameters)
Pin STRING [8] PIN of the SIM card inserted in the SIM card
The parameter is not relevant if the PIN was correctly
configured. If the PIN was incorrectly configured, the