EasyManuals Logo

Siemens CSM 1277 Safety Programming Guideline

Siemens CSM 1277
48 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #11 background imageLoading...
Page #11 background image
2 Configuring Fail-Safe Controllers
Safety Programming Guideline
Entry ID: 109750255, V1.0, 10/2017
11
Siemens AG 2017 All rights reserved
2.4 F-change history
F-change history acts like the standard user program's change history. In the
project tree, "Common data > Logs", one F-change history is created for each
F-CPU.
F-change history logs the following:
F-collective signature
User name
Compile time stamp
Download of the safety program with time stamp
Compiled F-blocks with signature and time stamp
Figure 2-6: F-change history
Recommendation
Activate change history when you start configuring or at the latest when you have
defined the final project-specific CPU name as the change history is linked to the
CPU name.
Figure 2-7: Activating F-change history