4 Optimizing Safety Programs
Safety Programming Guideline
Entry ID: 109750255, V1.0, 10/2017
41
Siemens AG 2017 All rights reserved
4.1.2 Timer blocks
Timers are an integral part of a safety program as many of the system functions
such as "ESTOP1" internally use these timers. Despite this fact, generating a fail-
safe time value requires considerable effort and regeneration for each single timer
block.
Recommendation
Reduce the number of timer blocks to a minimum.
4.1.3 Multi-instances
Recommendation
Use multi-instances for fail-safe function blocks. This means that the block-internal
tags are integrated into the block interface of the calling block.
Advantages
Standardization of safety programs:
No global data is used for block tags. This allows reuse of the calling block
(including the integrated blocks).
Optimizing the compile performance:
Using multi-instances requires less protection code than using instance
data blocks.
The use of multi-instances reduces the number of F-blocks on the system
side. This optimizes the compilation of the safety program.

Other manuals for Siemens CSM 1277

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CSM 1277 and is the answer not in the manual?

Siemens CSM 1277 Specifications

General IconGeneral
BrandSiemens
ModelCSM 1277
CategoryController
LanguageEnglish

Related product manuals