EasyManuals Logo

Siemens CSM 1277 Function Manual

Siemens CSM 1277
527 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #503 background imageLoading...
Page #503 background image
Instructions
9.4 PID basic functions
PID control
Function Manual, 03/2017, A5E35300227-AC
503
9.4.5.4
Input paramters TCONT_S
Table 9- 23 Input paramters TCONT_S
Parameters
Ad-
dress
Data
type
Default
Description
CYCLE 0.0 REAL 0.1 s At this input, you enter the sampling time for the controller.
CYCLE ≥ 0.001
SP_INT 4.0 REAL 0.0 The input "Internal setpoint" is used to specify a setpoint.
The valid values depend on the sensors used.
PV_IN 8.0 REAL 0.0 At the "Process variable input" you can assign parameters
to a commissioning value or you can interconnect an ex-
ternal process value in floating-point format.
The valid values depend on the sensors used.
PV_PER 12.0 INT 0 The process value in I/O format is interconnected with the
controller at the "Process value I/O" input.
DISV 14.0 REAL 0.0 For feedforward control, the disturbance variable is inter-
connected to the "Disturbance variable" input.
LMNR_HS 18.0 BOOL FALSE The signal "Control valve at high endstop" is interconnect-
ed on the input "High endstop signal of position feedback".
• LMNR_HS=TRUE: The control valve is at high end-
stop.
LMNR_LS 18.1 BOOL FALSE The signal "Control valve at low endstop" is interconnect-
ed on the input "Low endstop signal of position feedback".
• LMNR_LS=TRUE:
The control valve is at low endstop.
LMNS_ON 18.2 BOOL TRUE
Manipulated value signal processing is switched to manual
mode at the "Enable manual mode of manipulated signal".
LMNUP 18.3 BOOL FALSE In manual mode of manipulated signals, the output pa-
rameter QLMNUP is operated at the input parameter "Ma-
nipulated signal up".
LMNDN 18.4 BOOL FALSE In manual mode of the manipulated signals, the output
parameter QLMNDN is operated at the input parameter
"Manipulated signal down".
See also
Block diagram TCONT_S (Page 501)

Table of Contents

Other manuals for Siemens CSM 1277

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CSM 1277 and is the answer not in the manual?

Siemens CSM 1277 Specifications

General IconGeneral
BrandSiemens
ModelCSM 1277
CategoryController
LanguageEnglish

Related product manuals