Commissioning
4.3 Commissioning
Converter with Control Units CU230P-2; CU240B-2; CU240E-2
Getting Started, 04/2014, A5E32885834B AB
39
Settings in the basic commissioning menu
Basic commissioning
The "Basic commissioning" wizard sets the most important data for commissioning the drive.
The number of commissioning steps depends on the particular Control Unit.
Proceed as follows to carry out basic commissioning of the inverter:
1. Start the menu: WIZARD / BASIC COMMISSIONING, and set the following:
[0] V/f with linear characteristic
The motor data is pre-assigned using the motor code.
Observe the motor connection (star / delta)!
Enter the motor data for 50 Hz
Enter [V] according to the motor rating plate
Enter [A] according to the motor rating plate
Enter [kW] (or [hp]) according to the motor rating plate
Enter [rpm] according to the motor rating plate
16. Motor data ID [1] Stationary and rotating measurement
1)
If the motor cannot freely rotate, e.g. if travel is
mechanically limited, select the setting [2] "MotID only
p1900
Encoder type not activated
19. Macro device Select a pre-defined setting, see Section: Default
settings of the terminal strip (Page 28)
p0015
20. Minimum speed Enter the minimum speed [rpm], above which the motor
p1080
21. Ramp-up Time [s] in which the motor should accelerated from
standstill up to the maximum speed (p1082).
p1120
22. Ramp-down Time [s] in which the motor should be decelerated from
the maximum speed (p1082) down to standstill.
p1121
23. Motor temperature
Enter type of temperature sensor p0610