Functions
5.4 Setpoint sources
CU240S and CU240E Control Units, FW 3.2
102 Operating Instructions, 03/2009, A5E02440075B AA
Using BICO technology, you can also assign the JOG function to other keys.
Table 5- 24 Parameter to assign the JOG function to another button
Parameters Description
P0003 = 3 3: Expert
P1055 = ... Enable JOG CW
Possible sources: 722.x (digital inputs) / 19.8 (JOG key on the Operator Panel) /
r2090.8 (serial interface)
P1056 = ... Enable JOG CCW
Possible sources: 722.x (digital inputs) / 19.8 (JOG key on the Operator Panel) /
r2090.9 (serial interface)
5.4.6 Specifying the motor speed via the fieldbus
Specifying the motor speed via the fieldbus
To specify the speed of the motor via the fieldbus, the inverter must be connected to a
higher-level control via the STARTER software tool. For more information, see "Operation in
fieldbus systems".