Functions
Optimized, flexible automation station for HVAC and building automation and control
systems
System functions (alarming, scheduling, trending, access protection with individually
definable user profiles and categories)
Integrates data points and/or subsystems via Modbus RTU
Integration of wired M-bus meters via RS485 level-converter:
Offline and/or online engineering with ABT Site. No additional M-bus tool required
Primary and/or secondary device addressing
The following functions are available with KNX PL-Link bus:
Communication with RDG2..KN room thermostats, sensors, and operator units
Plug-and-play connection of Siemens field devices with KNX PL-Link
Engineering and commissioning with the ABT Site Tool using graphical function charts
Freely programmable. All function blocks, available in libraries, can be graphically
connected.
BTL tested BACnet communication on MS/TP, in compliance with the BACnet standard
including B-BC profile (Rev. 1.16)
IT security including HTTPS, IEC-62443 4-2 (Security Level 2), and BACnet Secure
Connect
BACnet Secure Connect support as BACnet/SC node
Generic operation via embedded web interface
WLAN interface for engineering and commissioning
Operating voltage AC 24 V or DC 24 V
Direct connection of field devices
DIN rail or screw mounting
Plug-in screw terminal blocks
Type summary
PXC4.M16 variants
1)
PXC4.M16S PXC4.M16
Order number S55375-C109 S55375-C101
Number of inputs and outputs (Onboard) 16 16
  Number of universal inputs and outputs (UIO) 12 12
  Number of relay outputs (DO) 4 4
Number of inputs and outputs (Onboard + TXM) up to 40 up to 40
Number of integration data points
(Modbus RTU)
0 up to 40
Total number TXM-I/Os and integration DPs 40
2)
80
2)
Number of KNX PL-Link devices 0 up to 64
2)
Number of configurable RS485 interfaces for Modbus RTU
integration
0 1
Number of M-bus meters wired via level converters (RS485)
3)
0 up to 250
1)
For details on engineering, see PXC4, PXC5 & PXC7 Planning overview, A6V13054435.
2)
KNX PL-Link data points do not count as integration points. For KNX PL-Link, only the limits on BACnet objects
are considered.
3)
The limitation is given by the maximum number of integration data points and maximum number of BACnet
objects.